Technical data TDE 25 T TDE 25 TDE 65 TDE 95
Article no. 1.410.000.100 1.410.000.105 1.410.000.115 1.410.000.120
Heating performance kW 3 3 6-9-12 9 - 13.5 - 18
Heating performance kcal max 2,586 2,586 10,300 15,400
Input voltage 230 V/50 Hz 230 V/50 Hz 400 V/50 Hz 400 V/50 Hz
Current consumption max. 13.4 A (3 kW) 13.4 A (3 kW) 18 A (12 kW) 27.2 A (18 kW)
Air flow rate 250 m³/h 250 m³/h 600 m³/h 1,520 m³/h
Temperature increase ΔT 36 °C 36 °C 60 °C 35 °C
Air pressure 40 Pa 40 Pa 130 Pa 110 Pa
Connection for power supply ø 155 mm 155 mm 300 mm 300 mm
Overheating protection yes yes yes yes
Sound level (distance 3 m) 55 dBA 55 dBA 63 dBA 67 dBA
Mobility portable portable moveable moveable
Thermostat inclusive accessory accessory accessory
Length mm 279 279 610 470
Width mm 254 254 356 406
Height mm 305 305 445 578
Weight kg 9.2 9.2 25 32

Technical data TDE 200 TDE 300 TDE 400
Article number 1.410.000.150 1.410.000.155 1.410.000.160
Heating performance 40 kW (34,394 kcal) 80 kW (68,788 kcal) 120 kW (103,181 kcal)
Air flow rate max. 3,000 m³/h 6,000 m³/h 9,000 m³/h
Air pressure 600 hPa
Blow out temperature max.* 60 °C
Temperature increase (∆T) max. 60 °C
Fan radial / 1,5 kW radial / 4 kW radial / 5,5 kW
Control Eight-stage switch for air flow rate and temperature
Stufe 0 Air flow rate 3,000 m³/h 6,000 m³/h 9,000 m³/h
Temperature increase (∆T)
Stage 1 Air flow rate 3,000 m³/h 6,000 m³/h 9,000 m³/h
Temperature increase (∆T) 15 °C
Stage 2 Air flow rate 3,000 m³/h 6,000 m³/h 9,000 m³/h
Temperature increase (∆T) 28 °C
Stage3 Air flow rate 3,000 m³/h 6,000 m³/h 9,000 m³/h
Temperature increase (∆T) 40 °C
Stage 4 Air flow rate 2,000 m³/h 4,000 m³/h 6,000 m³/h
Temperature increase (∆T)
Stage 5 Air flow rate 2,000 m³/h 4,000 m³/h 6,000 m³/h
Temperature increase (∆T) 15 °C
Stage 6 Air flow rate 2,000 m³/h 4,000 m³/h 6,000 m³/h
Temperature increase (∆T) 30 °C
Stage 7 Air flow rate 2,000 m³/h 4,000 m³/h 6,000 m³/h
Temperature increase (∆T) 60 °C
Input voltage 400 V / 50 Hz
Power consumption max. 61 A (41.5 kW) 123 A (84 kW) 182 A (125.5 kW)
Fuse protection / plug 63 A / CEE 63 A, 5-pin 125 A / CEE 125 A, 5-pin 200 A / direct connection
Hose connection ø 450 mm 600 mm
Suitable for hose lengths up to 100 m 100 m 100 m
Mobility wheelable/ fork lift / crane
Sound level (distance 3 m) 75 dB (A)
76 dB (A)
78 dB (A)
Minimum cable diameter 16 mm² 70 mm² 95 mm²
Overheat protection yes
Length 1,980 mm 2,000 mm 2,300 mm
Width 800 mm 800 mm 950 mm
Height 1,300 mm 1,300 mm 1450 mm
Weight 300 kg 350 kg 480 kg
* the maximum blow out temperature for the standard model is automatically electronically limited to 60 °C .